| Distribution transformer and lateral protection | 11–13.8 kV systems | 15.5 kV class | Often offered for 50 Hz and 60 Hz systems; verify the specific cutout and fuse-link approval. | 95 kV BIL is a common reference value for this class. | Common catalog options include 8 kA or 10 kA symmetrical, depending on design and test basis. | Confirm system grounding, available fault current, fuse-link range, and coordination with upstream protection. |
| Medium-voltage feeder and transformer protection | 20–24.9 kV systems | 27 kV class | Check that the rating explicitly covers the local nominal frequency, usually 50 Hz or 60 Hz. | 125 kV BIL is a common reference value for this class. | Common catalog options include 8 kA, 10 kA, or 12.5 kA symmetrical; availability is product-specific. | Check maximum system voltage, insulation coordination, altitude derating, and the required short-circuit duty. |
| High-voltage distribution and sub-transmission applications | 33–34.5 kV systems | 38 kV class | Confirm 50 Hz or 60 Hz suitability in the technical data; do not infer frequency capability from voltage class alone. | 150 kV BIL is a common reference value for this class. | Common catalog options include 8 kA or 10 kA symmetrical, with higher ratings available for some designs. | Verify the tested interrupting rating at the applicable maximum voltage, plus creepage distance and pollution suitability. |
| Replacement cutout for an existing installation | Match the installed system and equipment nameplate | Must be equal to or greater than the applicable maximum system voltage | Match the network frequency and confirm compatibility with the existing fuse-link family. | Meet or exceed the installation’s specified BIL and insulation coordination requirements. | Must meet or exceed the calculated available fault current at the installation point. | Check mounting dimensions, terminal arrangement, live-part clearances, operating method, and local utility requirements. |