| Applicable Product Standard | Compliance with the latest applicable IEC or equivalent national standard | For AC disconnectors and earthing switches above 1 kV, require compliance with IEC 62271-102. For metal-enclosed switchgear assemblies, also evaluate IEC 62271-200 where applicable. | Declaration of conformity, type-test reports, routine-test procedures, and clearly identified standard editions | 15% |
| Rated Voltage Selection | Rated voltage compared with the system's maximum operating voltage | Common indoor medium-voltage classes include 3.6 kV, 7.2 kV, 12 kV, 17.5 kV, 24 kV, and 36 kV. The selected rating must not be lower than the system requirement. | Technical datasheet, nameplate drawing, insulation-coordination documentation, and project-specific calculation | 8% |
| Continuous Current Capacity | Rated normal current and temperature-rise performance | Typical indoor medium-voltage switchgear applications use ratings such as 630 A, 1250 A, 2000 A, or 3150 A. The rating must match the feeder or busbar design current with suitable margin. | Temperature-rise test report, rated-current declaration, conductor arrangement, and installation instructions | 8% |
| Short-Time Withstand Capability | Rated short-time withstand current and duration | Common project requirements include 16 kA, 20 kA, 25 kA, 31.5 kA, or 40 kA for 1 s or 3 s. The value must be equal to or greater than the calculated short-circuit duty. | Short-time withstand test report, peak withstand data, protection study, and coordination calculation | 12% |
| Insulation Performance | Power-frequency withstand voltage and lightning impulse withstand voltage | Values depend on the rated voltage and insulation coordination. For a 12 kV class, a commonly specified level is 28 kV power-frequency withstand and 75 kV lightning impulse withstand, subject to the applicable standard and configuration. | Dielectric type-test report, routine dielectric-test record, creepage-distance drawing, and insulation-coordination data | 12% |
| Mechanical Endurance | Number of operating cycles and mechanism reliability | Specify the required mechanical endurance class under IEC 62271-102. Higher-cycle designs are preferable for frequent-operation applications; manual and motor-operated mechanisms should be evaluated separately. | Mechanical endurance test report, operating-cycle specification, mechanism drawings, and maintenance schedule | 10% |
| Earthing-Switch Safety | Interlocking, position indication, and short-circuit making capability where required | The design should prevent unsafe switching sequences, provide clear OPEN/CLOSED/EARTHED indication, and include an earthing-switch rating appropriate to the system fault level when fault-making duty is specified. | Interlocking schematic, functional test records, position-indicator drawings, and earthing-switch type-test documentation | 12% |
| Indoor Environmental Suitability | Ambient temperature, altitude, humidity, condensation, and enclosure protection | IEC 62271-1 normal service conditions generally include an ambient temperature from −5 °C to +40 °C and an altitude not exceeding 1,000 m unless otherwise specified. Verify derating for harsher conditions. | Environmental service-condition declaration, altitude derating curves, enclosure data, and installation requirements | 8% |
| Ingress Protection and Internal Arc Coordination | IP rating and compatibility with the surrounding switchgear enclosure | Evaluate the required IP code under IEC 60529. The isolating switch should be assessed as part of the complete assembly, especially where internal-arc classification or compartment separation is required. | IP test report, enclosure drawings, compartment layout, and complete-switchgear internal-arc documentation where applicable | 8% |
| Production Quality and Traceability | Routine testing, inspection controls, material traceability, and quality management | Every completed unit should undergo documented routine checks appropriate to the product, including mechanical operation, wiring, insulation, and functional verification. Manufacturing controls should be traceable to serial number or batch. | ISO 9001 certificate, inspection and test plan, routine-test records, calibration certificates, and serial-number traceability | 7% |
| Lifecycle Support and Serviceability | Spare-parts availability, maintenance intervals, technical support, and documentation quality | Prefer suppliers able to provide operation manuals, installation drawings, spare-parts lists, recommended lubrication and inspection intervals, and long-term support for the expected service life. | Service manual, spare-parts commitment, training plan, warranty terms, response-time policy, and reference project documentation | 5% |
| Total Cost of Ownership | Purchase price plus installation, testing, maintenance, downtime, and replacement costs | Compare equivalent ratings and test scope rather than unit price alone. Include motor operators, auxiliary contacts, interlocks, commissioning, periodic inspection, and expected spare-parts expenditure. | Itemized quotation, lifecycle-cost model, maintenance-cost estimate, delivery schedule, and warranty conditions | 5% |