| Typical suburban distribution feeder | 12.47 kV system; 180 A normal load and 260 A peak load | Maximum available three-phase fault current at the installation: approximately 8 kA; grounded distribution system | Rated maximum voltage suitable for the system; continuous-current rating above peak load with allowance for growth; interrupting rating at least equal to the calculated fault duty | Coordinate phase and ground pickup settings with upstream and downstream devices; set the reclose sequence and lockout behavior to the utility protection plan |
| Higher-load, higher-fault urban feeder | 12.47 kV system; 500 A normal load and 650 A peak load | Maximum available fault current: approximately 16.8 kA; confirm the system X/R ratio and grounding method | Choose a continuous-current rating that covers peak and expected future load; select an interrupting and making capability that covers the calculated fault duty | Check thermal loading, protection coordination, operating duty, and whether the selected device can interrupt the maximum asymmetrical fault current |
| Rural radial feeder with a long line | 24.9 kV system; 90 A normal load and 140 A peak load | Fault current may vary substantially along the feeder; example values are 6 kA near the source and 1.2 kA near the remote end | Use the highest system voltage and maximum fault current at the recloser location to establish the voltage and interrupting ratings | Verify that protection can detect the minimum remote-end fault current; assess sensitive earth-fault protection, coordination, and reclosing for temporary faults |
| Feeder with distributed generation or possible reverse power flow | 12.47 kV system; 300 A normal load and 500 A peak load | Fault contribution and current direction may change with generation connected; calculate fault levels for relevant operating configurations | Rate the device for the highest applicable voltage, continuous load, and fault duty under all credible system configurations | Assess directional overcurrent protection, coordination with generation protection, reclosing restrictions, and synchronism-check requirements where applicable |
| Medium-voltage feeder on a 24.9 kV system | 24.9 kV nominal system; example peak load of 450 A | Example maximum available fault current at the installation: 9.5 kA; confirm whether the system is effectively grounded or uses another grounding arrangement | Use equipment with a rated maximum voltage appropriate for the system (commonly a 27 kV class); continuous and interrupting ratings must meet calculated site requirements | Confirm insulation level, grounding compatibility, phase and ground protection settings, control-power needs, and remote monitoring interfaces |
| Feeder on a 34.5 kV system | 34.5 kV nominal system; example peak load of 360 A | Example maximum available fault current at the installation: 7.8 kA; use the utility’s short-circuit study and grounding data | Use a rated maximum voltage suitable for the system (commonly a 38 kV class); verify continuous-current, interrupting, and insulation ratings | Check protection curves, reclosing duty, operating sequence, environmental conditions, and compatibility with the existing control and communications scheme |