| Very light duty | 2 kJ/kV | Short overhead feeders, lightly exposed distribution sections, or locations with relatively low expected discharge energy. | Select an arrester whose declared line-discharge energy capability is at least 2 kJ/kV for the specified duty and voltage class. | Continuous operating voltage (Uc/MCOV), rated voltage (Ur), nominal discharge current, residual voltage at the prospective current, and short-circuit withstand. | Keep connecting leads short and straight. Confirm that the arrester is coordinated with upstream insulation levels and protective devices. | Suitable for light exposure |
| Light-to-moderate duty | 3–5 kJ/kV | General medium-voltage overhead distribution with moderate lightning exposure and ordinary switching activity. | Use a declared energy capability above the calculated duty; do not infer energy capability from nominal discharge current alone. | Uc/MCOV, Ur, nominal discharge current, line-discharge class or equivalent energy declaration, residual voltage, and thermal recovery performance. | Install at transformer, cable-transition, and exposed line-entry points where reflected travelling waves may increase equipment stress. | Common distribution range |
| Moderate duty | 7–10 kJ/kV | Long overhead lines, areas with frequent lightning, mixed overhead-and-cable networks, or substations with significant switching transients. | Choose a higher-energy metal-oxide arrester after checking the system’s temporary overvoltage duration and expected multiple-discharge sequence. | Energy capability per kV, thermal charge transfer, Uc/MCOV, TOV withstand curve, residual voltage at 5 kA and 10 kA, and pressure-relief performance. | Provide a low-impedance earth connection. Coordinate arrester protective level with transformer or cable basic insulation level (BIL/LIWV). | Recommended for exposed feeders |
| Heavy distribution duty | 12–15 kJ/kV | High-lightning-density networks, long line sections with repeated surge exposure, and substations connected to extensive overhead systems. | Require a documented energy rating comfortably above the calculated duty and verify stability after repeated impulses. | Declared line-discharge energy, repetitive impulse capability, thermal stability, residual voltage, TOV withstand, leakage-current behavior, and sealing performance. | Use arrester placement at both equipment terminals and line entrances where necessary. Minimize phase and earth lead inductance. | Heavy-duty selection |
| High-energy substation duty | 20–25 kJ/kV | Major substations, high fault-level systems, long overhead lines feeding critical equipment, or networks exposed to severe multiple-stroke events. | Select only equipment with a clearly stated high-energy line-discharge capability and a suitable thermal recovery margin. | Energy per kV, charge-transfer capability, rated voltage, MCOV, TOV withstand for the actual grounding system, residual voltage, and short-circuit behavior. | Verify substation grounding impedance, separation distances, insulation coordination, and the effect of arrester lead length on the protected voltage. | High-energy application |
| Very high duty | 30–40 kJ/kV | Critical high-voltage installations with severe lightning exposure, substantial line-discharge energy, repeated impulses, or stringent availability requirements. | Use a project-specific insulation-coordination study and require independent test evidence or a manufacturer declaration matching the complete duty cycle. | Full energy and charge-transfer capability, thermal stability, TOV curve, residual-voltage curve, mechanical and pressure-relief ratings, and service monitoring provisions. | Consider parallel arrester arrangements only after current-sharing, grading, physical layout, and protection-coordination studies. Do not simply add units without engineering review. | Specialist engineering review |
| Voltage check example: 11 kV system | System-dependent | A solidly grounded 11 kV line-to-line system has approximately 6.35 kV line-to-earth voltage under normal conditions. | Select Uc/MCOV above the maximum continuous phase-to-earth operating voltage, while maintaining adequate protection level and TOV capability. | Typical calculation: 11 kV ÷ √3 ≈ 6.35 kV. The final Uc/MCOV must also account for voltage variation, grounding method, and neutral displacement. | A nominal “11 kV arrester” label is not sufficient by itself; verify the actual Uc/MCOV and Ur values in the datasheet. | Verify Uc/MCOV |
| Voltage check example: 22 kV system | System-dependent | A solidly grounded 22 kV line-to-line system has approximately 12.70 kV line-to-earth voltage under normal conditions. | Confirm that the selected Uc/MCOV is suitable for approximately 12.70 kV normal phase-to-earth operation and for the system’s TOV events. | Typical calculation: 22 kV ÷ √3 ≈ 12.70 kV. Check actual maximum system voltage, grounding factor, fault-clearing time, and residual voltage. | Ungrounded, impedance-grounded, or resonant-grounded systems may require a higher Uc/MCOV than the simple √3 calculation suggests. | Check grounding method |
| Energy verification formula | kJ/kV × selected voltage base | The energy figure must be interpreted using the same voltage basis stated in the technical documentation. | Compare the arrester’s declared energy capability with the calculated line-discharge duty using consistent units and the same test definition. | Example screening calculation: 10 kJ/kV × 20 kV = 200 kJ on a 20 kV reference basis. This is not a substitute for the complete manufacturer test definition. | Do not compare kJ/kV values from different test methods without confirming whether the value refers to rated voltage, MCOV, discharge voltage, or another reference. | Confirm test basis |
| Final procurement check | 2–40 kJ/kV range | Any application in which the calculated or specified line-discharge duty falls within this screening range. | Accept the arrester only when voltage rating, energy capability, protective level, TOV withstand, environmental rating, and short-circuit performance all satisfy the project requirements. | Confirm IEC 60099-4 compliance, declared test class, Uc/MCOV, Ur, nominal discharge current, residual voltage, energy or charge-transfer capability, and test certificates. | Record the installed location, grounding arrangement, lead lengths, expected lightning environment, inspection interval, and replacement criteria. | Ready for technical approval |