| 1 | Voltage and Current Capacity | Verify that the panel voltage rating and busbar ampere rating are suitable for the electrical system and the calculated continuous load. | Select a panel rated for the system voltage and with a main or bus rating that is not less than the design load. Continuous loads are commonly evaluated at 125% of the continuous load plus 100% of non-continuous loads, where required by the applicable electrical code. | Panel and assembly ratings; applicable electrical installation code |
| 2 | Interrupting Rating and SCCR | Check the circuit breaker interrupting rating and the panel short-circuit current rating against the available fault current at the installation point. | The interrupting rating must not be lower than the available short-circuit current. For an industrial control or power distribution assembly, the short-circuit current rating must also be adequate for the prospective fault current. | Circuit breakers: IEC 60947-2 or the applicable national product standard; assemblies: IEC 61439 where applicable |
| 3 | Safety Certification and Compliance | Confirm that the complete panelboard or distribution assembly has been evaluated by an accepted conformity-assessment body for the intended market. | Review the product marking, certificate scope, installation instructions, and approved breaker combinations. Do not assume that individually certified components automatically make the complete assembly certified. | Common references include IEC 61439 for low-voltage assemblies and UL 67 for panelboards, depending on jurisdiction |
| 4 | Enclosure Protection | Match the enclosure to exposure from dust, water, corrosion, impact, and accidental contact with energized parts. | For indoor dry locations, a basic protected enclosure may be sufficient. Wet, dusty, outdoor, washdown, or corrosive environments require a suitable IP code or enclosure type. The rating applies only when the enclosure is installed and used as specified. | IP ratings: IEC 60529; enclosure types: NEMA 250 or the applicable local classification system |
| 5 | Breaker Compatibility and Configuration | Check breaker frame, mounting method, pole arrangement, bus connection, neutral configuration, and available circuit spaces. | Use only breaker types and accessories listed or approved for the panel. Allow spare spaces for future circuits, and verify whether the design requires main protection, a main disconnect, surge protection, or residual-current protection. | Manufacturer-approved combinations and the applicable panelboard or assembly standard |
| 6 | Environmental and Thermal Conditions | Evaluate ambient temperature, altitude, humidity, condensation, ventilation, sunlight, vibration, and corrosive substances. | Confirm derating requirements when the ambient temperature, altitude, or enclosure arrangement exceeds the conditions used for the equipment rating. Avoid installing heat-producing devices tightly together unless the assembly instructions permit it. | Equipment temperature limits, installation instructions, and applicable derating requirements |
| 7 | Installation, Maintenance, and Future Expansion | Review working clearances, cable-bending space, termination temperature ratings, labeling, access control, and maintenance provisions. | Choose a panel that provides adequate space for conductor routing and torque-controlled terminations. Include circuit identification, protective barriers, a reliable grounding and bonding arrangement, and enough capacity for planned expansion. | Applicable electrical code, installation instructions, and occupational electrical-safety requirements |