| Standards reference | Defined by IEC 62423 in addition to the applicable requirements for Type A devices. | Defined by IEC 62423 in addition to the applicable requirements for Type A devices. |
| Residual-current waveforms detected | AC, pulsating DC, and specified composite residual currents associated with single-phase frequency converters. | AC, pulsating DC, smooth DC, and specified composite residual currents, including currents with frequencies up to 1 kHz under the standard’s test conditions. |
| Smooth DC capability | Designed to tolerate superimposed smooth DC residual current up to 10 mA under the applicable standard test conditions; it is not a substitute for Type B where smooth-DC detection is required. | Designed to detect smooth DC residual current, subject to the device’s rated residual operating current and applicable standard requirements. |
| Typical equipment examples | Some single-phase inverter-driven appliances, such as variable-speed washing machines, heat pumps, and air-conditioning equipment, when the equipment manufacturer specifies Type F. | Some three-phase frequency converters, variable-speed drives, photovoltaic inverters, and other converter-based equipment when the manufacturer or installation rules require detection of smooth DC residual current. |
| Common rated residual operating currents | 30 mA is commonly used where additional personal protection is required. Other ratings are available for different protection purposes and installation designs. | 30 mA devices are available for additional personal protection; other ratings may be used for equipment or installation protection as permitted by applicable rules. |
| Key selection consideration | Suitable only when the likely residual-current waveform and the equipment instructions are compatible with Type F. Confirm the required RCD type in the manufacturer’s documentation. | Consider where smooth DC or a broader range of residual-current waveforms may occur. Check the equipment instructions, local wiring rules, and the complete protection arrangement. |
| Important limitation | Not every inverter-based appliance requires Type F; selection depends on the equipment design and applicable installation requirements. | Not every inverter-based installation requires Type B. For example, some equipment incorporates residual-DC detection that may affect the required upstream RCD type, subject to local rules and manufacturer instructions. |
| Selection note: Choose an RCD type based on the equipment manufacturer’s instructions, the expected residual-current waveform, system configuration, and applicable local electrical regulations. Rated residual operating current and time-delay characteristics are product-specific; this comparison is general guidance, not a substitute for design verification. |