| 2LBS + Fused Transformer Feeder | Two ring cable load-break switches and one transformer feeder with fuses | Switches the two ring ways for network sectionalizing; isolates the transformer feeder | Current-limiting fuses typically protect the transformer feeder against short circuits; fuse operation may trip the associated switching mechanism, depending on design | Compact distribution substations supplying transformers where a fused feeder is suitable for the transformer rating and protection study |
| 2LBS + Circuit-Breaker Feeder | Two ring cable load-break switches and one circuit-breaker feeder | Ring switching and feeder switching with a circuit breaker capable of interrupting fault current within its rated duty | Protection relay, commonly using current transformers; voltage measurement or additional sensing may be included for specific schemes | Transformer or outgoing feeder applications that need relay-based protection, adjustable settings, or coordination with upstream protection |
| 3-Way Switch Configuration (LBS–LBS–LBS) | Three load-break switch ways, often arranged as two ring ways and one switchable outgoing way | Manual or motor-operated switching and sectionalizing; does not by itself provide circuit-breaker fault interruption on the outgoing way | Protection is determined by the connected equipment and upstream devices; a load-break switch is not a substitute for a circuit breaker for clearing fault current | Ring-network nodes where switching and isolation are required, with fault protection provided elsewhere in the network |
| 2LBS + 2 Circuit-Breaker Feeders | Two ring cable load-break switches and two circuit-breaker feeder units | Ring switching plus independent switching of two protected outgoing circuits | Separate relay protection can be applied to each breaker feeder; exact functions depend on the relay scheme and instrument-transformer arrangement | Sites with multiple outgoing feeders, such as larger commercial, industrial, or campus distribution networks |
| Sectionalizer or Bus-Coupler Configuration | A switching or circuit-breaker unit arranged to connect or separate bus sections or network sections | Opens or closes a normally open or normally closed point to support sectionalizing and supply restoration | May use a circuit breaker and relay where fault interruption or automatic operation is required; interlocking and control logic depend on the scheme | Networks designed to isolate a faulted section or transfer supply between sections, subject to system operating rules |
| Metering or Direct-Cable Connection Unit | Metering, cable connection, or voltage-transformer units combined with the required switching ways | Provides measurement or cable termination alongside isolation and switching functions selected for the installation | Measurement transformers and metering equipment support monitoring or billing; protection is provided by the associated fuse, breaker, relay, or upstream device as specified | Installations requiring electrical measurement, a dedicated cable connection, or additional functions within a compact substation |