| Compressed-air receiver | 8 bar(g) | At or below the vessel’s maximum allowable working pressure, commonly around 9–10 bar(g) for this example | Blocked outlet, compressor malfunction, or excessive heating | Opens automatically when system pressure reaches the calibrated set pressure and discharges excess air | Reduces the risk of vessel rupture and damage to connected equipment |
| Steam or hot-water system | 6–16 bar(g) | Selected in accordance with the boiler, vessel, or piping design pressure | Thermal expansion, loss of circulation, or closed isolation valves | Relieves steam or hot water before pressure exceeds the allowable design limit | Protects boilers, heat exchangers, piping, and personnel from overpressure events |
| Hydraulic power unit | 140–210 bar(g) | Usually set below the rated pressure of the weakest protected component | Actuator stall, blocked flow, or sudden load increase | Diverts hydraulic fluid back to the reservoir when the pressure threshold is exceeded | Prevents hose bursts, seal failure, pump overload, and actuator damage |
| Process pipeline | Depends on the process fluid and pipe rating | Set below the pressure rating of the protected piping and equipment | Pump deadheading, control-valve failure, or rapid valve closure | Releases or redirects fluid to a safe location when pressure rises above the set point | Limits mechanical stress, vibration, leakage, and pipe or fitting failure |
| Storage tank | Near atmospheric pressure or low pressure | Configured separately for pressure and vacuum protection | Tank filling, vapor generation, blocked vents, or liquid withdrawal | Relieves excess pressure and, where required, admits air or inert gas during vacuum conditions | Prevents tank deformation, collapse, product loss, and hazardous releases |
| Refrigeration system | Typically 5–30 bar(g), depending on refrigerant and temperature | Based on refrigerant properties, equipment design pressure, and applicable safety requirements | Condenser blockage, fire exposure, or trapped liquid thermal expansion | Discharges refrigerant when pressure reaches the approved protection threshold | Protects compressors, condensers, vessels, and refrigerant circuits from overpressure |